|
|
FAQs
- Q. What is a regulated Underground Storage Tank System?
- A. An underground storage tank system (UST) is a tank and any underground
piping connected to the tank that has at least 10 percent of its combined volume
underground. The federal UST regulations apply only to underground tanks and piping
storing either petroleum or certain hazardous substances.
- Q. What is the environmental concern about USTs?
- A. Until the mid-1980s, most USTs were made of bare steel, which is likely to corrode
over time and allow UST contents to leak into the environment. Faulty installation
or inadequate operating and maintenance procedures also can cause USTs to release
their contents into the environment. The greatest potential hazard from a leaking
UST is that the petroleum or other hazardous substance can seep into the soil and
contaminate groundwater, the source of drinking water for nearly half of all Americans.
A leaking UST can present other health and environmental risks, including the potential
for fire and explosion.
- Q. Do all underground tanks have to meet EPA regulations?
- A. The following USTs are excluded from regulation and, therefore, do not need
to meet federal requirements for USTs:
- Farm and residential tanks of 1,100 gallons or less capacity holding motor fuel used for noncommercial purposes
- Tanks storing heating oil used on the premises where it is stored
- Tanks on or above the floor of underground areas, such as basements or tunnels
- Septic tanks and systems for collecting storm water and wastewater
- Flow-through process tanks
- Tanks of 110 gallons or less capacity
- Emergency spill and overfill tanks
- Q. What are the state and federal regulatory requirements for USTs?
- A. The state regulations for USTs are found in the Arkansas Pollution
Control and Ecology Commission
Regulation 12. The federal regulations
(40 Code of Federal Regulations, Part 280, 281) are adopted by reference in Arkansas
Pollution Control and Ecology Commission
Regulation 12. In 1988, EPA issued regulations setting
minimum standards for new tanks (tanks installed after December 22, 1988) and requiring
owners of existing tanks (tanks installed before December 22, 1988) to upgrade,
replace or close them. The regulations are divided into three sections: technical
requirements, financial responsibility requirements and state program approval objectives.
- Q. Why are USTs required to have release detection?
- A. EPA designed part of the technical regulations for underground storage tanks (USTs)
to make sure releases or "leaks" from USTs are discovered quickly before
contamination spreads from the UST site. Owners and operators are responsible for
detecting leaks from their tanks and piping.
- Q. What tanks are required to have leak detection?
- A. All USTs must now have leak detection. USTs installed after December 22, 1988 must
have leak detection when they are installed. USTs installed before December 22,
1988 had compliance deadlines that varied with the age of the USTs. By December
22, 1993, all of these "older" USTs had to be in compliance with leak
detection requirements.
- Q. What are the approved leak detection methods?
- A. Owner/operators
of petroleum USTs must use at least one of the seven leak detection methods listed
below:
- Secondary containment and interstitial monitoring
involves placing a barrier between the UST and the environment. The barrier
provides "secondary" containment and can be a vault,liner or double-walled
structure. Leaked product from the UST is directed toward a monitor located
in the "interstitial" space between the UST and the outer barrier.
Interstitial monitoring methods range from a simple dip stick to automated vapor
or liquid sensors permanently installed in the system. New USTs holding hazardous
substances must use this method.
-
Automatic tank gauging systems use monitors permanently
installed in the tank. These monitors are linked electronically to a nearby
control device to provide information on product level and temperature. During
a test period of several hours when nothing is put into or taken from the tank,
the gauging system automatically calculates the changes in product volume that
can indicate a leaking tank.
-
Vapor monitoring senses and measures product vapor
in the soil around the tank and piping to determine the presence of a leak.
This method requires installation of carefully placed monitoring wells. Vapor
monitoring can be performed periodically using manual devices or continuously
using permanently installed equipment.
-
Groundwater monitoring senses the presence of
liquid product floating on the groundwater. This method requires installation
of monitoring wells at strategic locations in the ground near the tank and along
the piping runs. To discover if leaked product has reached groundwater, these
wells can be checked periodically by hand or continuously with permanently installed
equipment. This method is effective only at sites where groundwater is within
20 feet of the surface.
-
Statistical inventory reconciliation uses sophisticated
computer software to determine whether a tank system is leaking. The computer
conducts a statistical analysis of inventory, delivery and dispensing data collected
over a period of time and provided by the operator to a vendor.
- Manual tank gauging can be used only on tanks
2,000 gallons or smaller. This method does NOT work on tanks larger than 2,000
gallons or on piping. This method requires taking the tank out of service for
at least 36 hours each week to take measurements of the tank’s contents. Tanks
1,000 gallons or less can use this method alone. Tanks from 1,001 to 2,000 gallons
can use this method only when it is combined with periodic tank tightness testing
and only for 10 years after installation or upgrade of the UST. After 10 years,
these USTs must use one of the leak detection methods listed above in 1-5.
-
Tank tightness testing and inventory control combines
two methods. Tank tightness testing requires periodic tests conducted by vendors
who temporarily install special equipment that tests the soundness of the tank.
Tank tightness testing must be used in combination with inventory control. Inventory
control is an ongoing accounting system, like a checkbook, kept by the UST owner/operator
to detect leaks. Inventory control requires taking daily accurate measurements
of the tank’s contents and performing monthly calculations to prove that the
system is not leaking. Tank tightness testing and inventory control can be used
only for 10 years after installation or upgrade of an UST. After 10 years, these
USTs must use one of the leak detection methods listed above in 1-5.
- Q. What are the leak detection requirements for piping?
- A. The leak detection requirements for the two types of piping systems are:
-
Pressurized piping needs automatic line leak detectors
(these can be automatic flow restrictors, automatic flow shutoffs or continuous
alarm systems). Pressurized piping also needs one of the following: groundwater
monitoring, vapor monitoring, secondary containment and interstitial monitoring,
statistical inventory reconciliation or an annual tightness test of the piping.
-
Suction piping needs no leak detection if it meets
two design requirements: 1) piping slopes so that the product drains back into
the tank when suction is released, and 2) piping has only one check valve located
closely beneath the pump in the dispensing unit. Suction piping not meeting
these design requirements must use one of the following: tightness test of the
piping every 3 years, groundwater or vapor monitoring, secondary containment
and interstitial monitoring or statistical inventory reconciliation.
- Q. What are the upgrade requirements to prevent releases from
USTs installed prior to the implementation of the federal regulations, December
22, 1988?
- A. There are three areas that must be addressed by December 22,
1998 for these "existing" tank systems to be in compliance or these systems
must be properly closed. The three areas are:
- Corrosion protection for tanks and piping must
be provided by being constructed of noncorrodible material, having a corrosion-resistant
coating and having cathodic protection or the steel tank can be clad with a
thick layer of noncorrodible material (this option does not apply to piping).
There are three other options that existing tanks can choose from to comply
with the corrosion protection requirements:
- Add cathodic protection to a tank that has
been proven to be structurally sound. Cathodic protection can be provided
by adding an impressed current system that protects the UST by introducing
an electrical current into the soil around the UST. Cathodic protection
systems must be periodically inspected and tested.
- Add interior lining which is a thick layer
of noncorrodible material to the interior of the tank. This interior lining
must be periodically inspected.
- Combine cathodic protection and interior lining.
USTs using this option are not required to have the interior lining periodically
inspected.
- Spill protection must be provided by the addition
of catchment basins to contain spills and the use of good filling practices
when product is delivered to the USTs. Basically, a catchment basin is a bucket
sealed around the fill pipe.
- Overfill protection must be provided by following
good filling practices and the installation of overfill protection devices.
USTs must have one of the following devices that guard against overfills: automatic
shutoff devices, overfill alarms or ball float valves.
- Q. What are ten "new" tank standards for tanks installed after December 22, 1988?
- A. All USTs installed after December 22, 1988 must meet the following performance standards:
- Corrosion protection must be provided by meeting one of the following:
- Tank and piping completely made of noncorrodible material, such as fiberglass.
- Tank and piping made of steel having a corrosion-resistant coating AND having cathodic protection.
- Tank made of steel clad with a thick layer of noncorrodible material (this option does not apply to piping).
- Spill protection must be provided by having catchment basins installed at the time the USTs are installed.
- Overfill protection must be provided by having overfill protection devices installed at the time the USTs are installed.
- USTs must also be designed, constructed and installed in accordance with a national code of practice.
- Q. What are the corrosion protection requirements for "new"
or upgraded "existing" UST piping systems?
- A. Steel piping must have cathodic protection. Piping entirely made of (or enclosed in) noncorrodible
material does not need cathodic protection.
- Q. How do you properly close an UST?
- A. To properly close an UST:
- Notify the Regulated Storage Tank (RST) Division of the Arkansas Department
of Environmental Quality (ADEQ) 30 days before closing. ADEQ will provide
you with the proper forms.
- Use a contractor licensed by the RST Division for all closure procedures.
- Proper assessment of the tank excavation must be conducted to determine
if the tank has leaked and damaged the environment. If the tank has leaked,
appropriate notification must be given and corrective action must be taken.
- Proper closure procedures (according to a recommended code of practice)
must be followed to assure the tank system is emptied, cleaned, assessed and
closed in a safe and correct manner.
|
|