Regulated Storage Tanks (RST) Data Files
Storage Tank Details for This Facility
| Facility ID | AFIN | Location Name/Address | Temp Out | AG | UG | Leak | 1998 Compl |
|---|---|---|---|---|---|---|---|
| 32000025 | 32-00042 |
ENTERGY INDEPENDENCE PLANT 555 POINT FERRY RD NEWARK, AR 72562 County: INDEPENDENCE |
X | X | X | X |
| Contact Name: | ANDY WILSON | Date Received: | 10/22/2020 |
| Contact Title: | SNR LEAD ENV ANALYST | Entry Date: | 03/22/1991 |
| Contact Phone: | (870) 698-4534 | Entry Clerk: | Jane Marsh |
| Location SIC: | Update Date: | 11/16/2020 | |
| Location AFIN: | 32-00042 | Update Clerk: | taylord |
| Latitude: | 35.678410 | Amended: | Y |
| Longitude: | -91.403863 | Certified Name: | RUSSELL B MCLAREN |
| Aboveground: | X | Title: | REPRESENENTATIVE |
| Underground: | X | Date Signed: | 10/19/2020 |
| Date Reg. Cert. Issued: | 7/17/2023 | Do not invoice, if marked: | [] |
| OwnerID | Owner Name/Address | Phone |
|---|---|---|
| 012597 | ENTERGY ARKANSAS, LLC 425 WEST CAPITAL AVENUE #27 LITTLE ROCK, AR 72201 |
(800) 368-3749 |
| County: | PULASKI | Last Date Updated: | 02/10/2021 |
| Owner Type: | 1 | Entry Clerk: | taylord |
| Date Form Received: | 01/18/2019 | Update Clerk: | fields |
| Date Form Entered: | 01/22/2019 |
| Date Signed | Financial Assurance Mechanism | Entry Clerk | Entry Date | Update Clerk | Update Date |
|---|---|---|---|---|---|
| 07/07/2008 | CIOU - Certificate issued, original, UST | fields | 07/07/2008 | ||
| 08/26/2011 | FAOF - Financial Assurance on file | MCNAIR | 11/16/2011 | ||
| 03/29/2019 | FAOF - Financial Assurance on file | fields | 04/01/2019 |
| Invoice # | Date Billed | Owner as of Billing Date | Status | Amount/ Date Due |
Last Amount Paid/ Last Date Paid |
Last Check # | Late Fee Billed | Total Paid |
|---|---|---|---|---|---|---|---|---|
| TKS001198 | 08/15/1990 | ARKANSAS POWER & LIGHT COMPANY | $140.00 08/15/1990 |
$140.00 08/16/1990 |
079422 | $140.00 | ||
| TKS005437 | 05/18/1991 | ARKANSAS POWER & LIGHT COMPANY | $105.00 06/30/1991 |
$105.00 07/09/1991 |
064275 | $105.00 | ||
| ABT000097 | 05/21/1991 | ARKANSAS POWER & LIGHT | $70.00 06/30/1991 |
$73.50 06/11/1992 |
05-4096 | $3.50 | $73.50 | |
| TKS010410 | 06/13/1991 | ARKANSAS POWER & LIGHT COMPANY | Void | 07/28/1991 |
||||
| TKS010604 | 09/16/1991 | ARKANSAS POWER & LIGHT COMPANY | Void | 10/31/1991 |
||||
| ABT001293 | 05/23/1992 | ARKANSAS POWER & LIGHT COMPANY | $35.00 06/30/1992 |
$35.00 08/10/1992 |
07-3126A | $35.00 | ||
| TKS011268 | 05/23/1992 | ARKANSAS POWER & LIGHT COMPANY | $105.00 06/30/1992 |
$105.00 08/04/1992 |
07-3125 | $105.00 | ||
| ABT001971 | 06/01/1992 | ARKANSAS POWER & LIGHT COMPANY | $35.00 06/30/1992 |
$35.00 08/10/1992 |
07-3126A | $35.00 | ||
| ABT002970 | 06/01/1993 | ARKANSAS POWER & LIGHT COMPANY | $95.00 06/30/1993 |
$95.00 07/09/1993 |
06-4326 | $95.00 | ||
| TKS016818 | 06/01/1993 | ARKANSAS POWER & LIGHT COMPANY | $142.50 06/30/1993 |
$142.50 07/09/1993 |
06-4326 | $142.50 | ||
| ABT004763 | 06/01/1994 | ARKANSAS POWER & LIGHT COMPANY | $100.00 06/30/1994 |
$100.00 06/13/1994 |
060837 | $100.00 | ||
| TKS022512 | 06/01/1994 | ARKANSAS POWER & LIGHT COMPANY | $150.00 06/30/1994 |
$150.00 07/12/1994 |
064075 | $150.00 | ||
| ABT006397 | 06/01/1995 | ARKANSAS POWER & LIGHT COMPANY | $100.00 07/16/1995 |
$100.00 07/19/1995 |
259607 | $100.00 | ||
| TKS027928 | 06/01/1995 | ARKANSAS POWER & LIGHT COMPANY | $150.00 07/16/1995 |
$150.00 07/20/1995 |
259608 | $150.00 | ||
| ABT007920 | 05/17/1996 | AP& L ATTN: RICK MCCABE | $100.00 06/30/1996 |
$100.00 06/24/1996 |
486015 | $100.00 | ||
| TKS034445 | 05/17/1996 | AP& L ATTN: RICK MCCABE | $150.00 06/30/1996 |
$150.00 06/24/1996 |
486163 | $150.00 | ||
| ABT009570 | 05/16/1997 | AP& L ATTN: RICK MCCABE | $100.00 06/30/1997 |
$100.00 06/18/1997 |
701068 | $100.00 | ||
| TKS038228 | 05/16/1997 | AP& L ATTN: RICK MCCABE | $150.00 06/30/1997 |
$150.00 06/18/1997 |
701068 | $150.00 | ||
| ABT011274 | 05/15/1998 | AP& L ATTN: RICK MCCABE | $100.00 06/30/1998 |
$100.00 06/26/1998 |
1031368 | $100.00 | ||
| TKS043357 | 05/15/1998 | AP& L ATTN: RICK MCCABE | $150.00 06/30/1998 |
$150.00 06/26/1998 |
1031367 | $150.00 | ||
| ABT013174 | 05/14/1999 | AP& L ATTN: RICK MCCABE | $100.00 06/30/1999 |
$100.00 06/11/1999 |
2130110 | $100.00 | ||
| TKS048945 | 05/14/1999 | AP& L ATTN: RICK MCCABE | $150.00 06/30/1999 |
$150.00 06/11/1999 |
2130110 | $150.00 | ||
| ABT014831 | 06/04/1999 | AP& L ATTN: RICK MCCABE | Void | 07/19/1999 |
||||
| ABT015250 | 05/19/2000 | AP& L ATTN: RICK MCCABE | Void | 06/30/2000 |
||||
| ABT016883 | 05/19/2000 | AP& L ATTN: RICK MCCABE | $100.00 06/30/2000 |
$105.00 12/12/2000 |
3333564 | $5.00 | $105.00 | |
| TKS053776 | 05/19/2000 | AP& L ATTN: RICK MCCABE | $150.00 06/30/2000 |
$150.00 06/15/2000 |
3223730 | $150.00 | ||
| ABT018735 | 04/12/2001 | A P & L ATN: RICK MCCABE | Void | 05/27/2001 |
||||
| ABT020406 | 05/18/2001 | A P & L ATN: RICK MCCABE | Void | 07/01/2001 |
||||
| TKS057953 | 05/18/2001 | A P & L ATN: RICK MCCABE | $150.00 07/01/2001 |
$150.00 07/17/2001 |
PCE1308 | $150.00 | ||
| TKS061899 | 05/17/2002 | A P & L ATN: RICK MCCABE | $150.00 06/30/2002 |
$150.00 06/27/2002 |
3693420 | $150.00 | ||
| TKS066695 | 05/09/2003 | ENTERGY ARKANSAS/ATN:RICK MCCABE | $150.00 06/30/2003 |
$150.00 06/09/2003 |
3919940 | $150.00 | ||
| ABT026390 | 05/14/2004 | ENTERGY ARKANSAS/ATN:RICK MCCABE | $100.00 06/30/2004 |
$100.00 06/09/2004 |
4586769 | $100.00 | ||
| TKS070443 | 05/14/2004 | ENTERGY ARKANSAS/ATN:RICK MCCABE | $100.00 06/30/2004 |
$100.00 06/09/2004 |
4586769 | $100.00 | ||
| TKS074451 | 05/16/2005 | ENTERGY ARKANSAS - RICK MCCABE | $200.00 06/30/2005 |
$200.00 06/06/2005 |
4796249 | $200.00 | ||
| TKS079581 | 05/19/2006 | ENTERGY ARKANSAS - RICK MCCABE | $300.00 07/03/2006 |
$300.00 06/13/2006 |
4987922 | $300.00 | ||
| TKS084779 | 05/08/2007 | ENTERGY ARKANSAS - RICK MCCABE | $300.00 06/30/2007 |
$300.00 05/24/2007 |
5168446 | $300.00 | ||
| TKS089984 | 05/15/2008 | ENTERGY ARKANSAS - RICK MCCABE | $300.00 06/30/2008 |
$300.00 06/17/2008 |
5374557 | $300.00 | ||
| TKS095077 | 05/11/2009 | ENTERGY ARKANSAS - RICK MCCABE | $300.00 06/30/2009 |
$300.00 05/29/2009 |
5562590 | $300.00 | ||
| TKS100213 | 05/17/2010 | ENTERGY ARKANSAS - RICK MCCABE | $300.00 06/30/2010 |
$300.00 06/20/2010 |
052510EFT | $300.00 | ||
| TKS105396 | 05/17/2011 | ENTERGY ARKANSAS - RICK MCCABE | $300.00 06/30/2011 |
$300.00 06/04/2011 |
Card | $300.00 | ||
| TKS110963 | 05/14/2012 | ENTERGY ARKANSAS - RICK MCCABE | $300.00 06/30/2012 |
$300.00 06/02/2012 |
EFT # 051412 | $300.00 | ||
| TKS116209 | 05/15/2013 | ENTERGY ARKANSAS INC, ENV MGMT | $300.00 06/30/2013 |
$300.00 05/26/2013 |
EFT# 150513 | $300.00 | ||
| TKS121363 | 05/14/2014 | ENTERGY ARKANSAS INC, ENV MGMT | $300.00 06/30/2014 |
$300.00 06/22/2014 |
EFT# 1379237 | $300.00 | ||
| TKS126456 | 05/06/2015 | ENTERGY ARKANSAS INC | $300.00 06/30/2015 |
$300.00 06/14/2015 |
EFT# 1499989 | $300.00 | ||
| TKS131671 | 05/23/2016 | ENTERGY ARKANSAS INC | $300.00 06/30/2016 |
$300.00 06/19/2016 |
EFT# 1639167 | $300.00 | ||
| TKS136791 | 05/16/2017 | ENTERGY ARKANSAS INC | $300.00 06/30/2017 |
$300.00 06/10/2017 |
EFT# 1768759 | $300.00 | ||
| TKS141705 | 05/15/2018 | ENTERGY ARKANSAS INC | $300.00 06/30/2018 |
$300.00 08/11/2018 |
EFT | $300.00 | ||
| TKS145206 | 01/22/2019 | ENTERGY ARKANSAS, LLC | $300.00 02/21/2019 |
$300.00 02/20/2019 |
card | $300.00 | ||
| TKS146628 | 05/14/2019 | ENTERGY ARKANSAS, LLC | $300.00 06/30/2019 |
$300.00 06/02/2019 |
CARD | $300.00 | ||
| TKS151581 | 05/13/2020 | ENTERGY ARKANSAS, LLC | $300.00 06/30/2020 |
$300.00 06/09/2020 |
EFT/CC | $300.00 | ||
| TKS156374 | 05/10/2021 | ENTERGY ARKANSAS, LLC | $150.00 06/30/2021 |
$150.00 06/22/2021 |
EFT/CC | $150.00 | ||
| TKS161218 | 05/10/2022 | ENTERGY ARKANSAS, LLC | $150.00 06/30/2022 |
$150.00 06/14/2022 |
EFT/CC | $150.00 | ||
| TKS166219 | 05/10/2023 | ENTERGY ARKANSAS, LLC | $150.00 06/30/2023 |
$150.00 06/07/2023 |
EFT/CC | $150.00 |
| Latitude: | Entry Date: | ||
| Longitude: | Entry Clerk: | ||
| Capacity: | 25000 | Update Date: | 09/11/1991 |
| Update Clerk: | MARSH |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Tank Status: | Permanently Out Of Use | Empty: | Steel: | ||
| Tank Status Changed Date: | 05/20/1991 | Diesel: | X | Epoxy: | |
| Status Changed Reason: | Removed | Kerosene: | Composite: | ||
| Install Date: | 01/01/1987 | Gasoline: | FRP: | X | |
| Site Assessment Date: | Used Oil: | Concrete: | |||
| Site Assessment Leak Check: | New Oil: | Interior Liner: | |||
| CERCLA Name: | Hazardous: | Excavation Liner: | |||
| Unknown: | Double Walled: | ||||
| Mixture Description: | Polyethylene Jacket: | ||||
| Other Description: | Unknown: | ||||
| Other: | |||||
| Release Detection | Corrosion Protection | Spill & Overflow Protection | |||
|---|---|---|---|---|---|
| Installed: | Installed: | Installed: | |||
| Manual Tank Gauging: | Ext. Asphalt Coating: | Spill Catchment Basin: | |||
| Tank Tightness Test: | Ext. Dielectric Coating: | Auto Shutoff Valve: | |||
| Inventory Controls: | Ext. FRP: | Auto Flow Restrictor: | |||
| Auto Tank Gauging: | Internal Lining: | Auto High Level Alarm: | |||
| Vapor Monitoring: | Cathodic Prot. System: | Unknown: | X | ||
| Groundwater Monitoring: | Electrical Isolation: | Other Description: | |||
| Interstitial/Dbl Wall: | Unknown: | X | |||
| SIR: | Other Description: | ||||
| Unknown: | X | ||||
| Other Description: | |||||
| Piping Material | Piping Type | Release Detection | |||
|---|---|---|---|---|---|
| Bare Steel: | X | Suction; PCV: | Vapor Monitoring: | ||
| Galvanized Steel: | Suction; TCV: | Groundwater Monitoring: | |||
| FRP: | Pressure: | Line Tightness Test: | |||
| Copper: | Gravity: | Auto Leak Detector: | |||
| Dbl. Walled: | Unknown: | X | Interstitial Monitoring: | ||
| Sec. Cont: | Repair Date: | Unknown: | X | ||
| Unknown: | Other Description: | Other Description: | |||
| Other Description: | |||||
| Piping Corrosion Protection |
Certificate of Compliance Testing Information |
||
|---|---|---|---|
| Coated/Wrapped: | Date: | ||
| FRP: | Company License Number: | ||
| Cathodic Prot. System: | Tester License Number: | ||
| Electrical Isolation: | Install Date: | ||
| Unknown: | X | Company License Number: | |
| Other Description: | Installer License Number: | ||
| Latitude: | Entry Date: | ||
| Longitude: | Entry Clerk: | ||
| Capacity: | 4000 | Update Date: | 09/11/1991 |
| Update Clerk: | MARSH |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Tank Status: | Permanently Out Of Use | Empty: | Steel: | ||
| Tank Status Changed Date: | 05/20/1991 | Diesel: | Epoxy: | ||
| Status Changed Reason: | Removed | Kerosene: | Composite: | ||
| Install Date: | 01/01/1987 | Gasoline: | X | FRP: | X |
| Site Assessment Date: | Used Oil: | Concrete: | |||
| Site Assessment Leak Check: | New Oil: | Interior Liner: | |||
| CERCLA Name: | Hazardous: | Excavation Liner: | |||
| Unknown: | Double Walled: | ||||
| Mixture Description: | Polyethylene Jacket: | ||||
| Other Description: | Unknown: | ||||
| Other: | |||||
| Release Detection | Corrosion Protection | Spill & Overflow Protection | |||
|---|---|---|---|---|---|
| Installed: | Installed: | Installed: | |||
| Manual Tank Gauging: | Ext. Asphalt Coating: | Spill Catchment Basin: | |||
| Tank Tightness Test: | Ext. Dielectric Coating: | Auto Shutoff Valve: | |||
| Inventory Controls: | Ext. FRP: | Auto Flow Restrictor: | |||
| Auto Tank Gauging: | Internal Lining: | Auto High Level Alarm: | |||
| Vapor Monitoring: | Cathodic Prot. System: | Unknown: | X | ||
| Groundwater Monitoring: | Electrical Isolation: | Other Description: | |||
| Interstitial/Dbl Wall: | Unknown: | X | |||
| SIR: | Other Description: | ||||
| Unknown: | X | ||||
| Other Description: | |||||
| Piping Material | Piping Type | Release Detection | |||
|---|---|---|---|---|---|
| Bare Steel: | X | Suction; PCV: | Vapor Monitoring: | ||
| Galvanized Steel: | Suction; TCV: | Groundwater Monitoring: | |||
| FRP: | Pressure: | Line Tightness Test: | |||
| Copper: | Gravity: | Auto Leak Detector: | |||
| Dbl. Walled: | Unknown: | X | Interstitial Monitoring: | ||
| Sec. Cont: | Repair Date: | Unknown: | X | ||
| Unknown: | Other Description: | Other Description: | |||
| Other Description: | |||||
| Piping Corrosion Protection |
Certificate of Compliance Testing Information |
||
|---|---|---|---|
| Coated/Wrapped: | Date: | ||
| FRP: | Company License Number: | ||
| Cathodic Prot. System: | Tester License Number: | ||
| Electrical Isolation: | Install Date: | ||
| Unknown: | X | Company License Number: | |
| Other Description: | Installer License Number: | ||
| Latitude: | Entry Date: | 03/22/1991 | |
| Longitude: | Entry Clerk: | ||
| Capacity: | 8000 | Update Date: | |
| Update Clerk: |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Tank Status: | Permanently Out Of Use | Empty: | Steel: | ||
| Tank Status Changed Date: | 09/04/1990 | Diesel: | Epoxy: | ||
| Status Changed Reason: | Removed | Kerosene: | Composite: | ||
| Install Date: | 01/01/1987 | Gasoline: | FRP: | X | |
| Site Assessment Date: | Used Oil: | X | Concrete: | ||
| Site Assessment Leak Check: | New Oil: | Interior Liner: | |||
| CERCLA Name: | Hazardous: | Excavation Liner: | |||
| Unknown: | Double Walled: | ||||
| Mixture Description: | Polyethylene Jacket: | ||||
| Other Description: | Unknown: | ||||
| Other: | |||||
| Release Detection | Corrosion Protection | Spill & Overflow Protection | |||
|---|---|---|---|---|---|
| Installed: | Installed: | Installed: | |||
| Manual Tank Gauging: | Ext. Asphalt Coating: | Spill Catchment Basin: | |||
| Tank Tightness Test: | Ext. Dielectric Coating: | Auto Shutoff Valve: | |||
| Inventory Controls: | Ext. FRP: | Auto Flow Restrictor: | |||
| Auto Tank Gauging: | Internal Lining: | Auto High Level Alarm: | |||
| Vapor Monitoring: | Cathodic Prot. System: | Unknown: | X | ||
| Groundwater Monitoring: | Electrical Isolation: | Other Description: | |||
| Interstitial/Dbl Wall: | Unknown: | X | |||
| SIR: | Other Description: | ||||
| Unknown: | X | ||||
| Other Description: | |||||
| Piping Material | Piping Type | Release Detection | |||
|---|---|---|---|---|---|
| Bare Steel: | X | Suction; PCV: | Vapor Monitoring: | ||
| Galvanized Steel: | Suction; TCV: | Groundwater Monitoring: | |||
| FRP: | Pressure: | Line Tightness Test: | |||
| Copper: | Gravity: | Auto Leak Detector: | |||
| Dbl. Walled: | Unknown: | X | Interstitial Monitoring: | ||
| Sec. Cont: | Repair Date: | Unknown: | X | ||
| Unknown: | Other Description: | Other Description: | |||
| Other Description: | |||||
| Piping Corrosion Protection |
Certificate of Compliance Testing Information |
||
|---|---|---|---|
| Coated/Wrapped: | Date: | ||
| FRP: | Company License Number: | ||
| Cathodic Prot. System: | Tester License Number: | ||
| Electrical Isolation: | Install Date: | ||
| Unknown: | X | Company License Number: | |
| Other Description: | Installer License Number: | ||
| Latitude: | Entry Date: | ||
| Longitude: | Entry Clerk: | ||
| Capacity: | 12000 | Update Date: | 01/08/2004 |
| Update Clerk: | MARSH |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Tank Status: | Permanently Out Of Use | Empty: | Steel: | ||
| Tank Status Changed Date: | 12/20/2003 | Diesel: | Epoxy: | ||
| Status Changed Reason: | Removed | Kerosene: | Composite: | ||
| Install Date: | 01/01/1987 | Gasoline: | FRP: | ||
| Site Assessment Date: | Used Oil: | X | Concrete: | X | |
| Site Assessment Leak Check: | New Oil: | Interior Liner: | |||
| CERCLA Name: | Hazardous: | Excavation Liner: | |||
| Unknown: | Double Walled: | ||||
| Mixture Description: | Polyethylene Jacket: | ||||
| Other Description: | Unknown: | ||||
| Other: | |||||
| Release Detection | Corrosion Protection | Spill & Overflow Protection | |||
|---|---|---|---|---|---|
| Installed: | Installed: | Installed: | |||
| Manual Tank Gauging: | Ext. Asphalt Coating: | Spill Catchment Basin: | |||
| Tank Tightness Test: | Ext. Dielectric Coating: | Auto Shutoff Valve: | |||
| Inventory Controls: | Ext. FRP: | Auto Flow Restrictor: | |||
| Auto Tank Gauging: | Internal Lining: | Auto High Level Alarm: | |||
| Vapor Monitoring: | Cathodic Prot. System: | Unknown: | X | ||
| Groundwater Monitoring: | Electrical Isolation: | Other Description: | |||
| Interstitial/Dbl Wall: | Unknown: | X | |||
| SIR: | Other Description: | ||||
| Unknown: | X | ||||
| Other Description: | |||||
| Piping Material | Piping Type | Release Detection | |||
|---|---|---|---|---|---|
| Bare Steel: | Suction; PCV: | Vapor Monitoring: | |||
| Galvanized Steel: | Suction; TCV: | Groundwater Monitoring: | |||
| FRP: | Pressure: | Line Tightness Test: | |||
| Copper: | X | Gravity: | Auto Leak Detector: | ||
| Dbl. Walled: | Unknown: | X | Interstitial Monitoring: | ||
| Sec. Cont: | Repair Date: | Unknown: | X | ||
| Unknown: | Other Description: | Other Description: | |||
| Other Description: | |||||
| Piping Corrosion Protection |
Certificate of Compliance Testing Information |
||
|---|---|---|---|
| Coated/Wrapped: | Date: | ||
| FRP: | Company License Number: | ||
| Cathodic Prot. System: | Tester License Number: | ||
| Electrical Isolation: | Install Date: | ||
| Unknown: | X | Company License Number: | |
| Other Description: | Installer License Number: | ||
| Latitude: | Entry Date: | 09/11/1991 | |
| Longitude: | Entry Clerk: | MARSH | |
| Capacity: | 15000 | Update Date: | 11/16/2020 |
| Update Clerk: | taylord |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Tank Status: | Permanently Out Of Use | Empty: | X | Steel: | |
| Tank Status Changed Date: | 10/14/2020 | Diesel: | X | Epoxy: | |
| Status Changed Reason: | Removed | Kerosene: | Composite: | ||
| Install Date: | 05/21/1991 | Gasoline: | FRP: | X | |
| Site Assessment Date: | Used Oil: | Concrete: | |||
| Site Assessment Leak Check: | N | New Oil: | Interior Liner: | ||
| CERCLA Name: | Hazardous: | Excavation Liner: | |||
| Unknown: | Double Walled: | ||||
| Mixture Description: | Polyethylene Jacket: | ||||
| Other Description: | Unknown: | ||||
| Other: | |||||
| Release Detection | Corrosion Protection | Spill & Overflow Protection | |||
|---|---|---|---|---|---|
| Installed: | 05/21/1991 | Installed: | 05/21/1991 | Installed: | |
| Manual Tank Gauging: | Ext. Asphalt Coating: | Spill Catchment Basin: | |||
| Tank Tightness Test: | X | Ext. Dielectric Coating: | Auto Shutoff Valve: | ||
| Inventory Controls: | X | Ext. FRP: | X | Auto Flow Restrictor: | |
| Auto Tank Gauging: | Internal Lining: | Auto High Level Alarm: | |||
| Vapor Monitoring: | Cathodic Prot. System: | X | Unknown: | X | |
| Groundwater Monitoring: | Electrical Isolation: | Other Description: | |||
| Interstitial/Dbl Wall: | X | Unknown: | |||
| SIR: | Other Description: | ||||
| Unknown: | |||||
| Other Description: | |||||
| Piping Material | Piping Type | Release Detection | |||
|---|---|---|---|---|---|
| Bare Steel: | Suction; PCV: | Vapor Monitoring: | |||
| Galvanized Steel: | Suction; TCV: | Groundwater Monitoring: | |||
| FRP: | Pressure: | Line Tightness Test: | |||
| Copper: | Gravity: | Auto Leak Detector: | |||
| Dbl. Walled: | X | Unknown: | X | Interstitial Monitoring: | X |
| Sec. Cont: | Repair Date: | Unknown: | |||
| Unknown: | Other Description: | Other Description: | |||
| Other Description: | |||||
| Piping Corrosion Protection |
Certificate of Compliance Testing Information |
||
|---|---|---|---|
| Coated/Wrapped: | Date: | ||
| FRP: | X | Company License Number: | |
| Cathodic Prot. System: | Tester License Number: | ||
| Electrical Isolation: | Install Date: | ||
| Unknown: | Company License Number: | ||
| Other Description: | Installer License Number: | ||
| Latitude: | Entry Date: | 09/11/1991 | |
| Longitude: | Entry Clerk: | MARSH | |
| Capacity: | 2500 | Update Date: | 11/19/2020 |
| Update Clerk: | fields |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Tank Status: | Permanently Out Of Use | Empty: | X | Steel: | |
| Tank Status Changed Date: | 10/14/2020 | Diesel: | Epoxy: | ||
| Status Changed Reason: | Removed | Kerosene: | Composite: | ||
| Install Date: | 05/21/1991 | Gasoline: | X | FRP: | X |
| Site Assessment Date: | Used Oil: | Concrete: | |||
| Site Assessment Leak Check: | N | New Oil: | Interior Liner: | ||
| CERCLA Name: | Hazardous: | Excavation Liner: | |||
| Unknown: | Double Walled: | ||||
| Mixture Description: | Polyethylene Jacket: | ||||
| Other Description: | Unknown: | ||||
| Other: | |||||
| Release Detection | Corrosion Protection | Spill & Overflow Protection | |||
|---|---|---|---|---|---|
| Installed: | 05/21/1991 | Installed: | 05/21/1991 | Installed: | |
| Manual Tank Gauging: | Ext. Asphalt Coating: | Spill Catchment Basin: | |||
| Tank Tightness Test: | X | Ext. Dielectric Coating: | Auto Shutoff Valve: | ||
| Inventory Controls: | X | Ext. FRP: | X | Auto Flow Restrictor: | |
| Auto Tank Gauging: | Internal Lining: | Auto High Level Alarm: | |||
| Vapor Monitoring: | Cathodic Prot. System: | X | Unknown: | X | |
| Groundwater Monitoring: | Electrical Isolation: | Other Description: | |||
| Interstitial/Dbl Wall: | X | Unknown: | |||
| SIR: | Other Description: | ||||
| Unknown: | |||||
| Other Description: | |||||
| Piping Material | Piping Type | Release Detection | |||
|---|---|---|---|---|---|
| Bare Steel: | Suction; PCV: | Vapor Monitoring: | |||
| Galvanized Steel: | Suction; TCV: | Groundwater Monitoring: | |||
| FRP: | Pressure: | Line Tightness Test: | |||
| Copper: | Gravity: | Auto Leak Detector: | |||
| Dbl. Walled: | X | Unknown: | X | Interstitial Monitoring: | X |
| Sec. Cont: | Repair Date: | Unknown: | |||
| Unknown: | Other Description: | Other Description: | |||
| Other Description: | |||||
| Piping Corrosion Protection |
Certificate of Compliance Testing Information |
||
|---|---|---|---|
| Coated/Wrapped: | Date: | ||
| FRP: | X | Company License Number: | |
| Cathodic Prot. System: | Tester License Number: | ||
| Electrical Isolation: | Install Date: | ||
| Unknown: | Company License Number: | ||
| Other Description: | Installer License Number: | ||
| Latitude: | Entry Date: | ||
| Longitude: | Entry Clerk: | MARSH | |
| Capacity: | 15000 | Update Date: | 12/30/2003 |
| Update Clerk: | MARSH |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Install Date: | 01/01/1983 | Empty: | Steel: | X | |
| Tank Status: | In Use | Diesel: | Concrete: | ||
| Tank Status Date: | Kerosene: | Plastic: | |||
| Date Last Used: | Gasoline: | Unknown: | |||
| Removed: | Used Oil: | Other Description: | |||
| Gals Remaining: | 0 | Hazardous: | |||
| Unknown: | |||||
| Mixture Description: | |||||
| Other Description: | TURB. LUBE OIL | ||||
| Internal Corrosion Protection | External Corrosion Protection | Piping | |||
|---|---|---|---|---|---|
| Cathodic Prot. System: | Cathodic Prot. System: | Bare Steel: | |||
| Lining: | Painted: | X | Galvanized Steel: | ||
| None: | Plastic: | Plastic: | |||
| Unknown: | None: | Cathodic: | X | ||
| Other Description: | PAINTED | Unknown: | Unknown: | ||
| Other Description: | DIKED/SPILL CTL | Other Description: | |||
| Latitude: | Entry Date: | ||
| Longitude: | Entry Clerk: | MARSH | |
| Capacity: | 15000 | Update Date: | 01/08/2004 |
| Update Clerk: | MARSH |
| Status | Substance | Tank Material | |||
|---|---|---|---|---|---|
| Install Date: | 01/01/1983 | Empty: | Steel: | X | |
| Tank Status: | In Use | Diesel: | Concrete: | ||
| Tank Status Date: | Kerosene: | Plastic: | |||
| Date Last Used: | Gasoline: | Unknown: | |||
| Removed: | Used Oil: | Other Description: | |||
| Gals Remaining: | 0 | Hazardous: | |||
| Unknown: | |||||
| Mixture Description: | |||||
| Other Description: | TURB. LUBE OIL | ||||
| Internal Corrosion Protection | External Corrosion Protection | Piping | |||
|---|---|---|---|---|---|
| Cathodic Prot. System: | Cathodic Prot. System: | Bare Steel: | |||
| Lining: | X | Painted: | X | Galvanized Steel: | |
| None: | Plastic: | Plastic: | |||
| Unknown: | None: | Cathodic: | X | ||
| Other Description: | PAINTED | Unknown: | Unknown: | ||
| Other Description: | DIKED/SPILL CTL | Other Description: | |||
| Lust ID#: | 32-0028 | Entry Date: | 09/07/2011 |
| Date Notified: | 09/06/2011 | Entry Clerk: | BISSELL |
| Received By: | Bissell, Jack | Update Date: | 09/26/2011 |
| Update Clerk: | BISSELL |
| Leak Information Details: | |||
|---|---|---|---|
| Notifier Name: | Jack Bissell | Date: | 09/06/2011 |
| Address: | Amount: | ||
| City: | Substance: | Diesel, | |
| State: | Discovery: | INS | |
| Zip: | Cause: | ||
| Phone: | Damage: | ||
| Comments: DURING ROUTINE COMPLIANCE INSPECTION HIGH LEVEL ALARM LIGHT WAS ON FOR INTERSTITIONAL PROBE ON DIESEL TANK. SOUTHERN COMPANY WAS CONTACTED BY ANTHONY WILSON AT THE ENTERGY FACILITY ON 9/6/2011. EMAIL RESPONSE FROM BARRY WINNINGHAM AT SOUTHERN COMPANY STATES THAT SOUTHERN WILL PERFORM TANK TIGHTNESS TEST AND CHECK ALARM. [BISSELL 9/7/2011 2:11:24 PM]. ON 9/23/2011 SOUTHERN CO. REPAIRED CAP FOR INTERSTITIONAL PROBE AND PERFORMED A TANK TIGHTNESS TEST. iT WAS THE OPINION OF SOUTHERN CO. THAT THE CAP (SEAL) WAS ALLOWING WATER TO ENTER THE INTERSTITIONAL SPACE AND NOT A TANK LEAK. SUSPECTED LUST DENIED. [BISSELL 9/26/2011 1:44:23 PM]. | |||
| Lust ID#: | 32-0037 | Entry Date: | 07/24/2018 |
| Date Notified: | 07/24/2018 | Entry Clerk: | smcduffie |
| Received By: | McDuffie, Sam | Update Date: | 08/02/2018 |
| Update Clerk: | morganr |
| Leak Information Details: | |||
|---|---|---|---|
| Notifier Name: | TRIP GENTRY, ENTERGY ARKANSAS | Date: | |
| Address: | P.O. BOX 551 |
Amount: | |
| City: | LITTLE ROCK | Substance: | Diesel, |
| State: | AR | Discovery: | |
| Zip: | 72203 | Cause: | |
| Phone: | (501) 377-4032 | Damage: | |
| Comments: TRIP GENTRY, ENTERGY ARKANSAS, CALLED TO REPORT A HIGH LEVEL ALARM FOR THE INTERSTITIAL PROBE ON THE 15,000 GALLON DIESEL UST. WILL INVESTIGATE TO DETERMINE CAUSE. [Last modified by Sam McDuffie on 7/24/2018 3:49 PM] THE SOUTHERN CO. OF NLR VACUUM TESTED THE INTERSTITIAL SPACE ON THE 15,000 GALLON DIESEL ON JULY 27, 2018. TWO GALLONS OF WATER WAS REMOVED FROM THE INTERSTITIAL SPACE. THE WATER ENTERED THROUGH BRASS ADAPTER THREADS. THE SOUTHERN COMPANY RE-DOPED THE THREAD AND CLEANED THE CAP. THE SENSOR WAS ALSO REMOVED, TESTED, REPLACED, AND TESTED AGAIN. THERE WAS NO RELEASE INTO THE ENVIRONMENT SO THIS LUST IS BEING DENIED. [Last modified by Robert Morgan on 8/2/2018 10:59 AM] | |||